u/ebag_98

N4 migration 3.8-4.15

Has anyone even attempted this spam of a migration?

I performed this the other day and an odd thing happened. After commissioning the Jace with the migrated backup it would fail on the passphrase, it is the correct passphrase. I did the big file protection step and reset it. That part did work. But after that none of my station passwords worked. I ran the file locally and was able to login to station, with the same username and password! Will not login to station on Jace. Now I have a Jace that I can not log into. Maybe because it went too far in versions on the migration? Checked logs and no errors so I am out of ideas.

reddit.com
u/ebag_98 — 1 day ago

Sylk bus

I have a spyder 6438 and a SIO 6042. The devices are 4 devices from eol. When I download the program both thermostats (tr42) and inputs and outputs do not work on the sio. I have 18v on the sylk buss but the thermostats always say please load. I have no errors on the Jace. We did have bacnet communication issues but we replaced the bacnet wire and communication seems to be fixed.
What would cause the sio to not follow the commands or inputs? I replaced the sylk buss wire thinking it may be an issue. So far I have not found the issue.

reddit.com
u/ebag_98 — 1 month ago