New build HP, too warm!
ETA:
Settings I've changed following fantastic advice from everyone.
Lowered heat curve from 0.70 to 0.40 Lowered flow temp from 55 to 45 degrees Heating schedule tidied up to go from 18 to 20 degrees.
I've learned a lot from this post and will be making adjustments as I go from here.
Thank you!
Original post:
Hey folks,
Moved into a new build in June and finally done a bunch of research for the schedules and changed to a TOU tarrif to suit, tarrif starts on Thursday.
Vaillant arotherm, 3 bed end terrace.
What I'm noticing though is it's TOO warm.
I'd be extremely grateful if anyone can take the time to review my settings and make any suggestions to anything I might have missed.
I'm in Scotland. My control module is reading indoor temp 24 degrees, outdoor 16 degrees. The highest temp I have set is 21 degrees for a brief pre-heat.
Current schedule (we work day and nightshift from home):
Heating (setback is at 18):
Mode: time control
7 days
0000 - 0200 19 degrees
0200 - 0400 18 degrees
0400 - 0600 21 degrees
0600 - 1600 20 degrees
1600 - 1900 18 degrees
1900 - 2300 20 degrees
2300 - 2400 19 degrees
DHW:
Mode: time control
Temp: 55 degrees
7 days
0300 - 0400
1500 - 1600
Circulation:
7 days
0630 - 0830
1430 - 1600
1900 - 2100
Circuit 1 installer config:
Target flow: 0 degrees
OT switch off: 14 degrees
Heat curve: 0.70
Min flow: 15 degrees
Max flow: 55 degrees
Set back mode: normal
Room temp mod: active
I feel I've included more detail than needed just for heat but more the better, right?..
I'm a bit baffled how indoor temps are reaching 24 degrees.. It's hot in the whole house.
Thank you so much x