r/buildingscience

Pergola / carport post anchors for hurricane zone

Does anyone have any experience with hurricane rated post bases for a covered wood carport / pergola structure in Florida? Approx dimensions would be 10 feet x 20 feet

Was thinking of making posts by laminating three 2x6 x10s together vs using a 6x6…so post base would have to work with 4.5 x 5.5 dimensions

Can post bases be anchored into 6 inch thick driveway or do I need to cut concrete and embed post bases in some kind of poured concrete footing?

Thanks for any help!

I’m assuming all the posts should have knee braces as well….

reddit.com
u/Unique_Yak4659 — 7 hours ago
▲ 5 r/buildingscience+4 crossposts

Gap in perimeter wall sheathing

what do I do about this? I took over as my own contractor. They put 8’ osb and then a separate foot tall piece on top. I can see gaps like this many places throughout the home.

u/ksvaughn1979 — 1 day ago
▲ 3 r/buildingscience+2 crossposts

Best way to vent a range hood with a sloped A-frame ceiling?

I’m trying to figure out the cleanest way to add real exterior venting for the range in this kitchen.

The stove is under a sloped A-frame ceiling, so a normal wall-mounted hood doesn’t seem like an easy fit. I’m also getting the roof replaced this fall, so I’m hoping to sort this out now in case the best option involves a roof penetration.

Main things I’m trying to balance:

  • Good actual ventilation, not just a recirculating hood
  • Something that works with the angled ceiling
  • Not creating an awkward-looking interior setup
  • Keeping the exterior roof vent as subtle as possible

For anyone who has dealt with a similar setup, what would you do here? Custom hood, hood insert, ceiling-mounted option, sidewall vent, roof vent, or something else? Also interested in anything you’d avoid.

The red X's are the approximate location from the roofline to ceiling above the range.

u/corsilt — 22 hours ago
▲ 0 r/buildingscience+1 crossposts

Advice needed with vapor barrier

am a bit at a loss and don’t want to screw up here. We live in zone 5. Just had new siding put on (Hardie) which included 1/4” foam board underneath (I understand this is more for leveling than a vapor barrier). My problem is now the basement. I am doing a quick Reno. I discovered that the original owner used insulation with a plastic vapor barrier behind d the drywall. I removed the old ceiling tiles which were foil backed along with Kraft backed insulation in the joists. My plan was to spray everything black and leave it open. I discovered some mold near an exterior wall around Kraft backed insulation. I am certain that the initial install by the previous owner was done wrong.

Take a look at pics. Orlando I properly insulate this? The area is about 2-3 feet above foundation. The current vapor barrier stops at the top of the drywall. There is a gap to the exterior framing then this is where Kraft backed was added (and mold appeared). How do I properly insulate this? Rockwool up to finished wall without foam board? Lay foam board horizontally up to vapor barrier? I feel if I add foam board it will trap moisture here actually. Worried about both the exterior framing to the foundation as well as the interior cavity.

Any advice appreciated. I’m conflicted!

u/JustNuts27 — 21 hours ago
▲ 7 r/buildingscience+2 crossposts

How to insulate house???

This is a 1960 chicago house, with brick and concrete veneer it appears. I am replacing an exterior facing wall due to mold and condensation. Images attached of the issue, there looks to be furring strips and then the drywall was attached. No insulation at all. Right now I’m thinking closed cell foam applied to all the corner (only) and then moving up stud frame 1-2 inches from the brick for more air space. And then adding smart vapor barrier on the room facing side and then dry wall. Don’t want any further condensation risk so will leave it at that, will this work or better considerations????images

u/Successful_Pin8843 — 1 day ago

WUI ridge vent or alternative?

Climate 3A, just finished retrofitting Vulcan Vents’s eave vents as intakes (not pictured). I’m on the border of a WUI zone surrounded by a preserve. Just knowing of these products is beyond the scope of contractors for my area.

In the past year of researching products, I’ve not found specific ridge vent products meant that’d be ember resistant. The closest is Coravent’s 600-TE (pictured w/ VV’s continuous ridge vent for my style roof), though I have doubts with corrugated plastic being sufficiently fire resistant, plus it doesn’t have enough NFA for the aspect ratio of my roof. Also, there’s still a part of me that doesn’t trust the product enough to stop an ember’s ingress and ignite or smolder the sheathing.

“It’s not hard” to go pick up sufficiently dense wire screen from McMaster-Carr. Figuring out how to securely raise the ridge tile and have it live through yearly 40 mph winds, 60 mph gusts, is also a concern. Roof is currently concrete tile with a “not felt” underlayment from ‘94 when the house was made.

Interior ceilings are a mix of 8’, 10’, and half vaulted with a pitch going between the two. This makes it infeasible to convert the vented attic to a sealed, conditioned air space.

How’d you approach making a fire resistant ridge vent? If the individual products aren’t recognized as WUI listed, will this matter for insurance coverage?

u/DigitalCorpus — 20 hours ago

I need the air inside the home to flow using east to west trade winds due to severe Asthma/Allergies. I also want to use high ceilings and stacking to cool the home, AC would mean closed windows.

I am closing on a land purchase in the northwest of Puerto Rico (Aguadilla) and it will take at least 16 months from what I am told before I can get permits to build. My Asthma is chronic and I have slept in tents, in my car, on the floors of offices, been hospitalized numerous times,etc etc to find relief. Allergy shots did not wok, biologics did not work, and at 60 feeling I cannot last much longer I went to PR and slept outside on my friend's 2 acre property and after 10 days I was 90% better for the first time in my life. The only time I went indoors was to shower or eat. I had already rented at least 30 different apartments and homes in PR and other places and while opening windows helped, it was not enough. I need as close to outside ventilation as I can get. I will hire an architect of course, but I could not help using Claude to design something that would allow air to flow freely from East to West (trade winds) with windows open on both sides and no obstructions. I might even add some mechanical ventilation to draw air through. Thoughts on this approach?

u/Agitated-Whole2328 — 1 day ago

Attic Ventilation

I'm currently renovating a 1906 build house. I removed 100% of the insulation from the attic to re-wire, and reframe. The attic was 100% vermin, bug, and moisture free. Lots of layers of insulation, but probably around 30" total: 14" of blown fiberglass on top of 2-3 laters totaling 16" of cellulose. I have 1 turbine passive exhaust, and I had 2 open turtle intakes. I dug out 2 more that had been packed with bird nests/insulation.

I'm looking to install a whole house fan. The exhaust requirements are listed and easy to figure out, but I'm concerned about when the fan isn't running. I'll have 9 square feet of NFVA ridge vent for the fan , but when turned off I'm worried about the ratio of intake to exhaust. Any insight on balancing intake/exhaust with enough exhaust for a whole house fan?

reddit.com
u/Character-Okra4200 — 1 day ago

Vent direction and style

How much does vent direction and style affect air flow? I currently have vents with the gills (don’t know if that it the right term) the blow half left and half right. In some rooms that means they blow right toward the returns. Should I make changes to them?

reddit.com
u/Bazurkmazurk — 1 day ago
▲ 1 r/buildingscience+1 crossposts

Pole Building Insulation

Looking to understand the best way to insulate this building (western OH).

Moved into a new house last fall that came with this newly built detached garage/mini pole building. I park my wife’s car and my project car in the two car bay, and have a small teardrop under the mezzanine and some pedal bikes stashed in various places.

Id like to maintain some of the recessed space on the wall for storage, will likely finish out with OSB so I can hang some shelves/racks to get garden tools and bikes off the floor. Winter was brutally cold here and the building was unusable as far as hobby work. Also had issues with condensation on my tools and vehicles. Also had some issues with the posts sweating.

My thought is to use foam panels between the girts and OSB over the foam/girts. Do I need an air gap between the metal siding and the foam board? And the vapor barrier on the inside of the building, sandwiched between the foam/girts and OSB?

I am a total newbie, primarily want to make sure I don’t cause condensation/rot issues but would like the building to be more comfortable during the winter/summer extremes. I’m also on a budget so spray foam is probably not an option.

Thanks

u/ws6ryan — 1 day ago

We are building stairs to the second floor of this room inside a hangar. Privately owned and built by owner so we dont need to worry about code beyond best safety practices. My question is how should I best attach the stringers to the large metal cross member at the top of the wall?

u/whywouldthisnotbea — 2 days ago
▲ 15 r/buildingscience+1 crossposts

Invention: Radiant barrier ventilation prevent ice dam, ventilate roof and reflect radiant heat for homes

Hi everyone,
I invented this product and I do have patent pending but however I am stuck at marketing stage and need help with some ideas how to bring it to people’s home.
What it is: It is made from foam and Mylar( reflect 97% radiant heat)

Where to apply?
Apply between roof rafters under plywood sheathing. Sprayfoam can be apply under and still have airspace for radiant heat and air ventilation from soffit to the ridge vent.
It can be made 24” center or 16” center. Expandable to fit tightly between the rafter without too much effort.
Lightweight and diy install friendly.

Why we need this?
Typical roof for summer is extremely hot and in winter if you dont have cold roof ice dam can occur from the heat leakage melting the snow.
If you have sprayfoam insulation, if any roof leak it’s almost impossible to detect where and you may have to remove either the roof or the spayfoam.

How can this safe the home?
the radiant heat keep enter your home regardless what type of insulation you have. With the mylar ability to reflect all those radiant heat out and the airflow to bring those hear and humidity vent out of your home.
If you have a roof leak, you are most likely to able to detect it by looking at the color from water build up at the soffit.

I have a friend Corbett from Home Performance did a review for me on youtube if anyone interested to see. It is at 2:30 Minute
https://youtu.be/\_TicXBQkH2Q

Sorry for not having an actual video on the product yet. Still in production.

Thank you for reading this Reddit communities.

Sincerely
Huu

u/Choice-Clerk-1228 — 3 days ago

Air-conditioning seal: can I vent onto my open window.

I'm working out how to set up a seal on my window so I can get a portable air con unit.

Its a two pane window.

Top half is a hopper. Bottom half is sealed shut.

My plan is to get a polycarbonate sheet that covers both, with a hole cut where I fit the air con hose.

Given other obstacles in the area, it would be much better if I could fit the hose onto the bottom half of the sheet. However, it would then be blowing hot air directly on to the window, rather than directly out. It would still be on the other side of the "airlock" so would cool the room but is that going to be bad for the window?

reddit.com
u/Life-Selection5233 — 3 days ago

Latest thinking re: non-foam insulation in unvented Cape Cod cathedral ceilings?

Hi all. I am trying to wrap my mind around the latest thinking around insulating unvented short-slope cathedral ceilings in Cape Cods that open up to a small vented top attic above, and would really appreciate any guidance folks can provide!

I have read a lot of articles and presentations and posts and am still not quite sure I fully understand what is considered reasonably safe and why, especially when it comes to cellulose vs fiberglass and whether the insulation should be up against the roof deck or if there should be baffles. (I know there has been a fair amount of research in the last 10-15 years or so on this from places like BSC and Byggmeister, although I haven’t seen any updates since 2023ish and some of the findings seem confusing to me as a layperson.) Assuming a retrofit situation where rigid exterior foam and spray foam are off the table (which I understand are by far the safest and most code-compliant options), what are the least risky ways to handle sloped ceilings where the rafter bays open up to a top attic in region 4A?

— Is dense-pack cellulose in these slopes now considered reasonably safe as long as they open up to a top attic up above, based on recent research (such as New England’s Favorite Roof Retrofit: Moisture Data from Three MA Case Studies)? What are the most important factors to minimize risks in this situation? It’s important to make sure the cellulose is packed very densely, right? Does the ceiling drywall provide enough of an air barrier to keep moisture out (assuming no recessed lighting or other penetrations), or are there other steps that should be taken to protect against air/moisture traveling into those slopes in a retrofit situation? Does it matter if the top attic only has gable vents?

— What is the building science behind baffles/air gaps and whether insulation should touch the roof deck or not (in a situation without soffit vents from below, but where it’s an old house with a wood plank roof deck that probably has some outdoor air leaking in through cracks and gaps, and then the baffles go up into the vented top attic)? Does this differ for cellulose vs fiberglass? I would have thought that baffles would help or at least not hurt (except decreasing the R-value a little), but that doesn’t seem to align with the importance of making sure cellulose is really densely packed without any airflow. Or is it okay for the cellulose to be densely packed against baffles rather than the sheathing itself? Does it matter what the baffles are made out of?

— The modeling study “Moisture-Safe Unvented Wood Roof Systems” seems to suggest that faced fiberglass batts would be significantly safer than cellulose in a regular unvented rafter bay in zone 4 (table 3 on page 11)– does that sound right? But then is table 4 on that page saying that it is too risky because if air flows through the insulation there will be too much time with condensation potential at the roof deck? If so, is that still true in the Cape Cod situation where there is an attic above that the moisture can rise up into? How about if there are baffles? Is fiberglass generally considered safer or less safe than cellulose in these situations?

— Vapor diffusion ports are allowed in un-vented roofs as an alternative to foam in zones 1-3, but they were tested by BSC in zone 5 in MA and failed, correct? Have they ever been tested in zone 4A? Here near DC it feels like our climate (winter monthly average temps around 40) is closer to, say, Charlotte, than MA. I saw that ages ago Joe Lstiburek said he thought they would probably work in zone 4 but needed more testing– were they ever tested or was it assumed that the zone 5 testing went poorly enough that they should be avoided in zone 4 as well? Also, is the top attic of a Cape Cod considered to be kind of like a giant vapor diffusion port, and if so, does it matter if the attic only has gable vents and no ridge vents?

Thanks so much in advance for any insight you can share!

reddit.com
u/Risinglight0123 — 2 days ago
▲ 2 r/buildingscience+1 crossposts

Fixing moisture issues for detached garage/studio

I live in a century home on Long Island, NY that had a detached garage in the backyard. At some point past owners finished it up and converted it to a studio with carpeted floors. The studio is built on a concrete slab (not sure if theres any footings). The studio is right at the property line and so theres concrete on front, back, and right side while there's soil on the left. There's 4x4x4 PT lumber as the sill/bottom plate for the walls to stand on and I believe it is sitting square at the edge of the slab. The wall is then constructed such that sheathing is nailed to the studs down to the bottom plate, then foam board, and finally vinyl siding. All of this directly at grade so no concrete wall for the bottom plate to sit on. The stud bays have fiberglass insulation between them. Outside, there's a few conduits to run electricity to the shed.

The first problem is that one of the past owners put up a garden bed on the soil side. This meant that the soil side siding was actually below dirt. Over time from moisture it seems the bottom parts of the sheathing have rotted and have given way to termites and carpenter ants.

The second problem is that the monolithic concrete slab in the front of the studio cracked thereby creating a slight negative slope towards the structure. During heavy rainfalls the water pools and thus causing the same set of problems.

I was hoping to just use this space as a home office so trying to limit drastic changes to the structure while still being able to repair and prevent further damage.

I've called an exterminator who will drill holes in the concrete + trench the soil and do termite treatment. After waiting 48 hours we'll resume repair work with the following plan:

The Plan (Soil Side):

  1. Snap a level line 9.25” above the final dirt grade, removing/cutting away the rotted lower siding, foam, and sheathing.
  2. Install a 3/4" PVC trim sheet in place of the cut out sheathing. Top half screwed to the studs and bottom to the PT lumber. The sheet will go down to grade.
    1. Use liquid flashing like Flashmate to flash the seam between the concrete slab and PVC trim
    2. Slip aluminum z-flashing strip over the trim and under/behind the older sheathing, overhanging the PVC trim to shed water
  3. On the "older" wall right above the Z flashing strip, install new vinyl starter strip and reuse vinyl siding.
  4. On the inside if any insulation was cut, place foam board in the stud bay and fill with expanding foam. Will look for insect resistant products here.
  5. On the outside perimeter, dig a 1' wide and 4" deep trench that slopes away. Plat heavy duty landscape fabric and fill with river rocks to prevent muddy splash back and help with drainage during rains.

The Plan (Concrete Sides):

Follow the same plan as above however we'll cut the PVC trim just enough to leave about a 1/4" gap between it and the concrete slab. For that gap we'll use Sikaflex construction sealant.

For the corners we'll just overlap the trims together instead of doing a miter cut

Any glaring red flags with this plan?

Thanks in advance!

u/Najubhai — 3 days ago
▲ 0 r/buildingscience+1 crossposts

Crawlspace humidity question — is there any interpretation of these numbers that ISN'T a problem?

Looking for honest technical opinions, including counterarguments if you have them.

Setup: older house in Portland OR. Crawlspace under one bedroom, approximately 165 sq ft. Single ~3"x6" passive vent in one corner. Plastic sheeting on the ground but not sealed to the foundation walls in any way.

I've logged temperature and RH continuously in the crawlspace for 13 days using a data logger (30-min intervals, 180+ readings), paired with an outdoor sensor for comparison. Here's what I found:

  • Crawlspace averaged 75% RH, never dropped below 65% RH across the entire logging period
  • Outside air averaged 57% RH over the same period
  • I calculated absolute humidity (g/m³) for every paired reading — the crawlspace contained more absolute moisture than outside air in 100% of readings, averaging about 18% more water per cubic meter
  • This held through both hot sunny days and rainy days — not a weather-dependent spike, a sustained baseline condition

So I'm concluding that the high RH isn't simply warm outside air cooling down in the crawlspace — the absolute humidity data seems to show the crawlspace is generating its own moisture load, which I attribute to ground vapor.

A home inspector looked at it recently and described the humidity as "slightly elevated but within normal range, especially after a recent rain." Our data was collected across varied weather including hot sunny days well before and after any rain, so we're not sure how to reconcile that report with what we logged.

Specific questions:

  1. Is there any legitimate building science interpretation where sustained 75% average / 65% minimum RH in a crawlspace is NOT a problem?
  2. Does the absolute humidity data (crawlspace consistently wetter than outside air) change how you'd evaluate this?
  3. What would you recommend as a fix — noting that a simple exhaust fan seems unlikely to help in our Portland, OR climate where outside air in summer is already near saturation when cooled to crawlspace temps?

Context: we're renters raising this as a habitability concern (we've been having symptoms in the room above this crawlspace), so we're trying to understand whether the data we have is as significant as we think it is, or whether we're missing something. Genuinely open to being told we're wrong.

Thanks so much!

reddit.com
u/Low-Lawfulness6830 — 3 days ago
▲ 9 r/buildingscience+1 crossposts

Desperately need help with moisture in conditioned attic in zone 5

Hey guys, I'm really panicking and don't know where to turn.

I had a Heatpump system installed last October for heating and cooling in upstate New York Zone 5. It's ducted in the upstairs bedrooms+bathrooms, and mini splits everywhere else.

This April, I decided to try to fix some high heating bills (3000kwh for a really cold month) with an attic insulation. I had passive gables on a raised ranch, no vented soffits, and a few passive vents near the ridge. I had read somewhere briefly that I could condition the attic with spray foam, bringing the HVAC system inside the conditioned space, better air sealing, etc.

Then things went wrong.

An energy auditor company referred me to an insulation sub contractor (call them company A) who took me to r38 open cell foam and r22 closed cell on the gable walls. They sealed up the limited aforementioned vents before spraying.

What I have now is the following:

- I'm almost positive that open-cell was wrong in the roof deck because of roof rot concerns and code for my climate (dc315 ignition paint but NO vapor retarder paint). Minimum of a class 2 vapor barrier is required for zone's 5-8.

- they attempted to remove all of the visible old r13 fiberglass insulation in the ceiling joists, but did not use a vacuum, and half the attic has osb (where the air handler sits) that they did not access. Another company (call them company B) claims that the smell I get is from the spray foam residue mixed with fiber glass. They offered to remove it and do better air sealing on my ducts.

- attic humidity swings from 55 percent in the morning and can top out around 70% on the hottest part of the day. It doesn't seem to do this on cloudy days, and seems to correlate with the sun.

- I had company (B) come and do a blower door test and they claimed that my humidity was stack effect driven from my rim joists, and that the results of the blower door test indicated that I now need an ERV. The same company had previously quoted me to put an attic dehumidifier in in addition to removing the remaining fiberglass but now wants to do the ERV instead.

I attached an image from my humidistat, and I think my primary issue is solar vapor drive

During the blower door test when the house was under negative pressure, all of that attic smell came into the living space. My wife started coughing and had to leave the house or faint..I fared a little better but now I'm super concerned. We also have a young child.

I found the following building science: https://www.greenbuildingadvisor.com/article/high-humidity-in-spray-foam-attics which mirrored the problem I was having. They suggested cutting a supply for the attic or adding a dehumidifier. I don't see an ERV here. I feel like I have analysis paralysis and don't know what to do.

My goals:

- take a deep breath

- not be killed by my house

- resolve the moisture issues

- fix air quality issues

- fix vapor retarder.

Any advice on how to unpack this and move forward is invaluable and greatly appreciated

u/PrgrmMan — 5 days ago

I am building a small temporary 16x24 house in climate zone 5A. The last house I helped work on still used polyethylene interior vapor barrier. Help me pick the best wall assembly since so much has changed.

I read through the new IRC but I want a little better than the minimum. It will be 2x4 wall with R15 cavity and two inches of continuous exterior insulation. I am just not sure what is generally considered the best options now for 5A.

My proposed wall would be:

Sheetrock w/R15 faced batts OR rockwool with smart vapor barrier > Zip sheathing > 2 inch rockwool comfort board > 1x3 rainscreen > aluminum lap siding.

In my head this would work because it could dry either direction from the zip sheathing and with the continuous insulation ratio to wall cavity, it shouldn't have any condensation issues.

But would I be better to use 2 inch foil faced polyiso with taped seams instead of the rockwool comfort board? It would offer better insulation and additional waterproofing. If doing polyiso I could move a basically zero perm layer on the outside but then I feel like there could be drying issues between the zip and foil face of the polyiso?

reddit.com
u/RedditWoodworker — 4 days ago

How to prevent mold with engineered hardwood on concrete slab? Building home in humid PNW

My understanding is that concrete vents and cures over 30 years - and therefore needs to “breathe” and not sealed off completely. Is that true? Because if so, a glued down engineered hardwood floor would form a vapor seal that traps all the moisture underneath the floor.

We live on the PNW coast and moisture and humidity are key concerns. I’m thinking of putting down eco cork foam underlayment then floating engineering hardwood.

reddit.com
u/josh_moworld — 4 days ago
▲ 6 r/buildingscience+1 crossposts

Should I cover my Gable vents?

I had a ridge vent installed with my new roof. The house has good blown-in insulation in the attic, along with gable vents on both ends.

I also have aluminum soffit installed over the wood soffit, with every 4th piece a vented piece of soffit. After some investigation, I found there are no holes cut in the soffit to actually allow venting.

So, essentially I have 2 gable vents and a ridge vent, which I believe is giving me poor ventilation. My upstairs is always a struggle to keep as cool as my main level, and my AC always seems to be running on hot days.

My plan is to cut 3 or 4 inch holes in as many of the vented soffit pieces that I can, and install baffles in the attic.

Should I cover my gable vents after I do this, or are they ok to keep? I've read about it both ways, and I can't really find a consensus. Some say the gables are fighting the ridge, others say it helps with circulation.

I live in the Midwest, in a Zone 4 area, if that helps. Thanks!

reddit.com
u/turtal46 — 4 days ago